| Performance | Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Rated Airflow (m³/h) | High | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 | |
| Medium | 260 | 390 | 510 | 640 | 770 | 1020 | 1280 | 1530 | 1790 | ||
| Low | 170 | 260 | 340 | 430 | 510 | 680 | 850 | 1020 | 1190 | ||
| Rated Cooling Capacity (W / Kcal/h) | H | 1.8 | 2.7 | 3.6 | 4.5 | 5.4 | 7.2 | 9 | 10.8 | 12.6 | |
| H | 1548 | 2322 | 3096 | 3870 | 4644 | 6192 | 7740 | 9288 | 10836 | ||
| Rated Heating Capacity (Kw / Kcal/h) | H | 2.7 | 4.05 | 5.4 | 6.75 | 8.1 | 10.8 | 13.5 | 16.2 | 18.9 | |
| H | 2322 | 3483 | 4644 | 5805 | 6966 | 9288 | 11610 | 13932 | 16254 | ||
| Input Power (W) | 12Pa | H | 37 | 52 | 62 | 76 | 96 | 134 | 152 | 189 | 228 |
| 30Pa | H | 44 | 59 | 72 | 87 | 108 | 156 | 174 | 212 | 253 | |
| 50Pa | H | 49 | 66 | 84 | 100 | 118 | 174 | 210 | 250 | 300 | |
| Noise Level [dB(A)] | 12Pa | H | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
| 30Pa | H | 40 | 42 | 44 | 46 | 47 | 48 | 50 | 52 | 54 | |
| 50Pa | H | 42 | 44 | 46 | 47 | 49 | 50 | 52 | 54 | 56 | |
| Water Flow Rate (Kg/h) | 350 | 510 | 660 | 800 | 980 | 1280 | 1600 | 1920 | 2230 | ||
| Working Pressure (Kpa) | 30 | 30 | 30 | 30 | 40 | 40 | 40 | 40 | 50 | ||
| Number of Fans | 1 | 2 | 3 | 4 | |||||||
| Weight (Kg) | WA | 17 | 18 | 19 | 22 | 26 | 39 | 43 | 49 | 52 | |
| With return air box | 20 | 22 | 23 | 27 | 30 | 44 | 48 | 54 | 58 | ||
| Water Inlet/Outlet | 3/4”Internal Thread | ||||||||||
| Condensate Drain Pipe | 3/4”External Thread | ||||||||||
| Power Supply | 220V/50Hz | ||||||||||
| Notes | 1、Cooling conditions: Inlet air dry bulb temperature: 27°C, wet bulb temperature: 19.5°C; Inlet water temperature: 7°C, water temperature difference: 5°C. 2、Heating conditions: Inlet air dry bulb temperature: 21°C; Inlet hot water temperature: 60°C; Hot water flow rate is the same as cooling conditions. 3、Pressure test: Units are pressure tested at 2.0 MPa (20 bar), with a maximum allowable working pressure of 1.6 MPa (16 bar). 4、Others: Four-pipe systems are also available (e.g., 1-heating-2-cooling, 2-heating-2-cooling, 3-heating-1-cooling configurations). | ||||||||||
The FP-WA Horizontal Concealed Fan Coil Unit Series is engineered for discreet, high-capacity climate control in suspended ceilings. Offering superior airflow and quiet operation, it’s the ideal solution for offices, hotels, and commercial renovations where space and aesthetics are paramount.